본문 영역
Phosphate(PO4) Analyzer

-
1Convenient maintenance
- Easy tube replacement & disassembly
- Simplified structure
- Data storage function (USB)
-
27” Color LCD Monitor
-
3Display of data trend
-
4Grab sample analysis
-
5Automatic calibration by standard solution
-
6Multichannel operation (1∼3ch)
-
7Applications
- Control of chemical injection amount of corrosion inhibitor in power plant.
- Corrosion management of industrial boiler water and cooling water.
Technical Specifications
| Model | AP-05P |
|---|---|
| Measuring Principle | Colorimetric Method |
| Measuring Range | 0∼20.0 mg/L (ppm) |
| Display | 0.01 mg/L (ppm) |
| Accuracy | ±0.1 mg/L or ±5% |
| Response Time | 12 min App. |
| Calibration | Automatic by standard solution |
| Sample Pressure | 1∼5 bar |
| Sample Temperature | 5∼45 ℃ |
| Sample Flow | 200∼500 ml/min |
| Reagent Consumption | 60 days (A, B / 2 liter, STD Solution A, B / 2 liter) |
| Data Output | 4∼20 mA 2 ea, Alarm 2 ea, RS 485 Modbus (Option) |
| AUX ports | DI(2), DO(2), Option (AI, AO) |
| Panel Dimension (mm) | 400W X 500H X 200D (Flush, Wall mounting), 700W X 1700H X 400D (Standing type) |
| Degree of Protection | IP65( NEMA 4x) : Electronics, IP55(NEMA 4) : Wet part |
| Power | 100∼240 VAC (50/60 Hz) |
Analysis Flow
Installation
Dimensions of panel mounting
Dimensions of wall mounting
Consumable List (AP-05P Model)
| Part No. | Description | Replacement Cycle | Remarks |
|---|---|---|---|
| P05-010 | Reagent pump tube | 3 months | Tube set (A, B) |
| P05-011 | Fitting tube | 6 months | Reagent injection tube |
| P05-012 | Reagent bottle fitting | 1 year | Fitting and tube in bottle |
| P05-016 | Reagent A | 60 days | Reducing reagent (2 liter) |
| P05-017 | Reagent B | 60 days | Oxalic reagent (2 liter) |
| P05-019 | Standard solution A | 60 days | High Point (2 liter) |
| P05-020 | Standard solution B | 60 days | Low Point (2 liter) |
| P05-022 | Pump (Standard solution) | Failure | Supply pump for standard solution or grab sample |
| P05-023 | Pump (Reagent) | Failure | Supply pump for reagent |
| P05-035 | Sample filter | For preventing impurities inflow |